CE Power Cord Cable H05V-U H07V-U

Applicable to the cables and wires of rated yolatage 450/750V and less than 450/750V AC for power plant,household electrical applance,insurment and telecommunication equipment.

Download
Datasheet

CE Power Cord H05V-U

 

1. Application

It is used for the internal and peripheral hard wiring between the distribution board of electrical appliances and instruments and the wiring board of power distributor, and the interface between electronic and electrical equipment and switch cabinet. It is also suitable for power supply and lighting system. Fixed laying of exposed and embedded conduit

2. Cable Structure

Conductor: Single or stranded bare copper or tinned copper wire in accordance with IEC60228VDE 0295 Class5 standard
Insulation: PVC/TI1 according to DIN VDE 0281 Part 1+HD21.1
Color code: The wire core is identified by color and complies with HD402 standard
Application standards: HD21.3 S3, VDE-0281 Part-3, CE Low Voltage Directive, 73/23/EEC, and 93/68/EEC

CE POWER CABLE

3. Technical Parameter

Rated voltage: 30OV/500V
Test voltage: 4000V in accordance with DIN VDE0281 Part 2+HD21.2
Minimum bending radius fixed laying: 12.5XD (cable outer diameter)
Mobile installation: 12.5XD (cable outer diameter)
Fixed laying temperature range: -30 to+80 ℃
Mobile installation: -5 to+70 ℃
Flame retardancy: flame retardant and self-extinguishing
Complies with IEC60332-1-2+EN60332-1-2 ULvW-1+CSA FT1
Insulation resistance: 10MQ x km

4. Characteristics and Compliance

Characteristics: Solid single core wire,easy to peel,cut,easy to install,in line with the EU standard

CE Power Cord H07V-U

 

1. Application

It is used for the internal and peripheral hard wiring between the distribution board of electrical appliances and instruments and the wiring board of power distributor, and the interface between electronic and electrical equipment and switch cabinet. It is also suitable for power supply and lighting system. Fixed laying of exposed and embedded conduit

2.Cable Structure

Wire: Single or stranded bare copper or tinned copper wire in accordance with IEC60228VDE 0295 level 5 standard
Insulation: PVC/TI1 according to DIN VDE 0281 Part 1+HD21.1
Color code: The wire core is identified by color and complies with HD402 standard
Application standards: HD21.3 S3, VDE-0281 Part-3, CE Low Voltage Directive, 73/23/EEC, and 93/68/EEC

H07V-U CABLES

3. Technical Parameter

Rated voltage: 30OV/500V
Test voltage: 4000V in accordance with DIN VDE0281 Part 2+HD21.2
Minimum bending radius fixed laying: 12.5XD (cable outer diameter)
Mobile installation: 12.5XD (cable outer diameter)
Fixed laying temperature range: -30 to+80 ℃
Mobile installation: -5 to+70 ℃
Flame retardancy: flame retardant and self-extinguishing
Complies with IEC60332-1-2+EN60332-1-2 ULvW-1+CSA FT1
Insulation resistance: 10MQ x km

4. Characteristics and Compliance

Characteristics: Solid single core wire,easy to peel,cut,easy to install,in line with the EU standard

5. Data Reference
Voltage level(V)NominalNumber ofToplimit ofMaximum DCMinium insulationRecommendedReference
sectionconductorsoverallresistance (20℃)resistance (20℃)value of carringweight
(mm²)diameter(mm)(Ω/km)(MΩ·km)capacity(kg/km)
(A)
300/5000.512.3360.015138.3
0.7572.624.50.0121710.9
0.7512.724.50.0141711.8
172.818.10.0112013.7
11318.10.0132014.8
450/7501.513.212.10.0112520
1.573.312.10.012521.3
2.573.97.410.013431.5
2.5747.410.0093434.4
414.44.610.00854446.8
474.64.610.00774448.1
6153.080.0075865.1
675.23.080.00655868.8
1076.71.830.006579111
1677.81.150.005111166
2579.70.7270.005146263
35710.90.5240.004180356
501912.80.3870.0045228487
701914.60.2680.0035281679
951917.10.1930.0035344932
1203718.80.1530.00323971163
1503720.90.1240.00324561424
1853723.30.09910.00325191789
2406126.60.07540.00325922335
3006129.60.06010.0036852924
4006133.20.0470.00287993750

 